Mitigación de SAGS y SWELLS de una Red de Distribución IEEE de 30 Nodos Mediante la Ubicación de FACTS (SVC y DSTATCOM).

dc.contributor.advisorRivas Trujillo, Edwinspa
dc.contributor.authorCaicedo Ulloa, Juan Camilospa
dc.contributor.authorRoa Barragan, Jenny Elizabethspa
dc.creator.emailingjuancaicedo@gmail.comspa
dc.creator.emailjennyeli_14@hotmail.comspa
dc.date.accessioned2016-11-15T17:25:58Z
dc.date.available2016-11-15T17:25:58Z
dc.date.created2016-04-05spa
dc.descriptionEste trabajo de grado presenta un análisis y evaluación del comportamiento de una red de distribución en presencia de variaciones de tensión de corta duración, específicamente Sags (caídas de tensión) y Swells (aumentos de tensión), antes y después de la implementación de los compensadores SVC (Static Var Compensator) y DSTATCOM (Distribution Static Compensator), tomando como caso de estudio el sistema IEEE de 30 nodos, el cual presenta niveles de tensión similares a la red de distribución industrial y residencial Colombiana. Para ello se identifican los puntos críticos del sistema a partir del cálculo de una función objetivo que permite ver las variaciones de los perfiles de tensión durante la falla. Con los datos obtenidos se seleccionan dos nodos teniendo en cuenta algunos criterios. Con ayuda del programa DIgSILENT y un algoritmo implementado en MATLAB, se hace un análisis incluyendo las variaciones de tensión antes mencionadas, con magnitudes y duraciones que son seleccionadas con base en lo especificado en el estándar IEEE 1159:2009 y la norma NTC 5000:2013. Posteriormente se incluyen los compensadores en la red simulada y mediante índices referentes a niveles de tensión soportados en la normatividad Colombiana y el estándar IEEE mencionado, se evalúa el comportamiento de la red, verificando si luego de la compensación los niveles de tensión se encuentra dentro de los rangos aceptables que no afecten la calidad de energía, concluyendo que el sistema presenta mejoras con la implementación de los compensadores SVC y DSTACTOM para la mitigación de Sags y Swells en cada uno de los puntos críticos. Sin embargo, para variaciones de tensión con magnitudes de 1.3 p.u. el resultado no estuvo dentro de los rangos de tensión esperados, debido a la que la red cuenta con un condensador síncrono ubicado en el nodo 11 que inestabiliza el sistema e impide que los compensadores cumplan con el objetivospa
dc.description.abstractThis graduation project presents an analysis and evaluation about behavior of a distribution grid in presence of short duration voltage variation, specifically Sags (voltage diminutions or dips) and Swells (voltage elevations), before and after implementation of the compensators SVC (Static Var Compensator) and DSTATCOM (Distribution Static Compensator), taking as study case the IEEE 30 bus system, which presents similar voltage levels to the Colombian distribution grid (industrial and residential). For this, the critical points in the system are identified through using of an objective function that allows to look the profiles voltage during a fault. With the results obtained are selected two nodes taking into account certain criteria. Using the DigSILENT program an algorithm implemented in MATLAB, then is made an analysis including the voltage variations aforementioned, with magnitudes and durations that are selected with regard to specified in the IEEE 1159:2009 standard and the NTC5000:2013 norm. Then, are included the compensators and through standards of voltage levels supported in the Colombian norm and the IEEE standard aforementioned, the grid behavior is evaluated, checking if then compensation the voltage levels are within acceptable ranges that don’t affect the power quality. Finally it concludes that the system present improvements with the implementation of the SVC and DSTATCOM compensators for Sags and Swells mitigation in each of the critical nodes. However, for voltage variations with magnitudes 1.3 p.u. the result was not within the expected voltage ranges, due to the n grid has synchronous condensers located in the node 11 and 13, destabilizing the system and prevents compensating fulfill the objective.spa
dc.format.mimetypepdfspa
dc.identifier.urihttp://hdl.handle.net/11349/4318
dc.language.isospaspa
dc.rightsAtribución-NoComercial-SinDerivadas 4.0 Internacional*
dc.rights.accesoAbierto (Texto Completo)spa
dc.rights.accessrightsinfo:eu-repo/semantics/openAccessspa
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/*
dc.subjectFACTSspa
dc.subjectSVCspa
dc.subjectDSTATCOMspa
dc.subjectSwellspa
dc.subjectSagspa
dc.subject.keywordFACTSspa
dc.subject.keywordSVCspa
dc.subject.keywordDSTATCOMspa
dc.subject.keywordSwellspa
dc.subject.keywordSagspa
dc.titleMitigación de SAGS y SWELLS de una Red de Distribución IEEE de 30 Nodos Mediante la Ubicación de FACTS (SVC y DSTATCOM).spa
dc.title.titleenglishMitigation SAGS and SWELLS of a Grid Distribution IEEE 30-Node by Location of FACTS (SVC and DSTATCOM)spa
dc.type.coarhttp://purl.org/coar/resource_type/c_7a1fspa
dc.type.driverinfo:eu-repo/semantics/bachelorThesisspa

Archivos

Bloque original

Mostrando 1 - 1 de 1
Cargando...
Miniatura
Nombre:
CaicedoUlloaJuanCamilo2016.pdf
Tamaño:
7,87 MB
Formato:
Adobe Portable Document Format
Descripción:
Trabajo de Grado

Bloque de licencias

Mostrando 1 - 1 de 1
Cargando...
Miniatura
Nombre:
license.txt
Tamaño:
7 KB
Formato:
Item-specific license agreed upon to submission
Descripción: